The HIMatrix F1 DI 1601 SILworX is the SILworX version of HIMA's safety-related F1 DI 16 01 remote I/O (part no. 98 2200479). It provides 16 digital inputs, four pulsed outputs for input line monitoring and two switched Ethernet ports for safeethernet communication with a HIMatrix or HIMax controller.
Brand :
HIMAPart Number :
HIMatrix F1 DI 1601 SILworX / 98 2200479Weight :
0.7 kgDimension :
152 × 114 × 66 mm (W × H × D, without plugs)Description :
16-Channel Safety Digital Input Remote I/O for SILworXExpand the sections to review input signals, power, networking and installation data.
Maximum dimensions are specified without plugs: width includes enclosure screws, height includes the fixing bolt and depth includes the earthing screw. HIMatrix F1 DI 1601 SILworX mounts horizontally on a 35 mm DIN rail.
Source: HIMA HI 800 153 E, F1 DI 16 01 Manual, Rev. 1.01, sections 3.1–3.5 and 4.1–4.2. SILworX part no. 98 2200479: 0 to +60 °C.
HIMatrix F1 DI 1601 SILworX acquires 16 safety-related digital input states and sends them over safeethernet to a HIMatrix or HIMax controller. It is remote I/O, so the connected controller executes the safety application.
HIMA lists HIMatrix F1 DI 1601 SILworX as part no. 98 2200479 for SILworX engineering and operation from 0 to +60 °C. Match that article number and the hardware revision to the installed device.
HIMatrix F1 DI 1601 SILworX has 16 non-galvanically isolated digital inputs. HIMA specifies HIGH at 15–30 VDC and LOW at no more than 5 VDC; the installed sensor wiring and input configuration must match these levels.
HIMatrix F1 DI 1601 SILworX provides four pulsed outputs for configured input line monitoring, including short-circuit and open-circuit detection. They are test supplies for input circuits and must not be used as safety-related actuator outputs.
HIMatrix F1 DI 1601 SILworX uses a 24 VDC supply and two switched RJ-45 10/100Base-T Ethernet interfaces. Safety-related input data is exchanged with the connected controller over safeethernet within the configured HIMatrix network.
For HIMatrix F1 DI 1601 SILworX, provide HIMA part no. 98 2200479, quantity and the installed device label. Check the hardware and CPU OS revision, SILworX project, safeethernet settings, input wiring and required 0 to +60 °C range.
Official manufacturer-documentation status for HIMA HIMatrix F1 DI 1601 SILworX.
No current official HIMatrix F1 DI 1601 SILworX product datasheet was located in the manufacturer's public documentation. For product documentation and compatibility details, please contact Product Specialist Frida.
CONTACT FRIDASend the complete model, quantity, and your technical or purchasing question.
Technical reference: HIMA HI 800 153 E, F1 DI 16 01 Manual, Rev. 1.01, lists the SILworX execution as part no. 98 2200479. A direct manufacturer-hosted manual PDF was not confirmed in the public download library.
HIMatrix F1 DI 1601 SILworX is HIMA part no. 98 2200479, a 16-channel safety digital input remote I/O for SILworX engineering. It transmits field input states over safeethernet to the connected controller, which executes the safety application.
A clear workflow for sourcing, verification, shipment preparation, delivery and product assurance.
Include the complete part number, quantity and delivery destination.